Mark VX

ModelMark VX
Frame size160 ÷ 225
TechnologyANALOGUE
RegulatorVX
Part numberM00FA122A
ComplianceCE and UL unlisted
  • Main Data
  • Electrical characteristics
  • Features
  • Dimensions and weight

Main Data

Generator frame sizeStandard
160÷225
AVR supplyAuxiliary winding*,
mains
Voltage sensingSingle phase
Voltage remote controlArrangement
Radio interference supressorInternal
MARK VXM00FA122A
LimitersUnder-frequency

Electrical characteristics

Power supply voltage170 ÷ 277 Vac @ 50/60 Hz
Power supply sourceAuxiliary windings, mains
Voltage build-up5 Vac
Voltage sensing type1-phase
Voltage sensing range170 ÷ 277 Vac
Maximum continuative field current0 ÷ 5 Adc
Maximum forcing field current0 ÷ 8 Adc
Maximum field voltage100 Vdc
Field resistance8 Ω ÷ 20 Ω
Regulation accuracy from no load to full load±0.5 %
Accuracy with ±4% engine governing±1 %
Thermal Drift±0.5 %
Response time1 cycle
Operating temperature-30°C ÷ +70°C
Storage temperature-40°C ÷ +80°C

Features

InterfacePotentiometers
ProtectionUnder-frequency limiter
Internal fuse, replaceable
ControlExternal potentiometer, 100 kΩ - 1 W
External DC voltage signal (0-10 V)

Dimensions and weight

L160mm
B93.6mm
K137mm
H45mm
D5.5mm
Weight370g
Drawing